Hey,
added a check for Runtime againt Warning / Critical Values. Noticed that one of our UPS had a remaining runtime of 6! Minutes, but the Replacement Flag for the battery was not set.
case “runtime” { my $ups_runtime_ticks = query_oid($oid_runtimeleft); my $ups_runtime_mins = int($ups_runtime_ticks / 100 / 60); my $perf_data = “|’Runtime Remaining’=$ups_runtime_mins,$warning_threshold,$critical_threshold;;”;
if ($ups_runtime_mins > $warning_threshold) { print “OK, (Runtime remaining: $ups_runtime_mins minutes)$perf_datan”; exit $OKAY; } elsif ($ups_runtime_mins > $critical_threshold) { print “Warning, (Runtime remaining: $ups_runtime_mins minutes)$perf_datan”; exit $WARNING; } else { print “Critical, (Runtime remaining: $ups_runtime_mins minutes)$perf_datan”; exit $CRITICAL; }
#print “MINUTES: $ups_runtime_minutesn”; #exit $OKAY; }
Host File:
define service{ use local-service ; Name of service template to use host_name service_description RUNTIME check_command check_apc!runtime -w 20 -c 10 }