Checks working mode (online, bypass, offline, ...) on CPQUPS-MIB SNMP compatible Hewlett-Packard (HP) UPS devices.
Current Version
0.1b
Last Release Date
July 21, 2011
Owner
Vicente Gavara
Website
http://www.boreal-labs.com
Download URL
http://www.boreal-labs.com/joomla/index.php/en/downloads-menu/view.download/23-hp-compaq/48-checkcpqupsmode.html
License
GPL
Compatible With
This plugin checks the working mode on a CPQUPS MIB compliant HP UPS device. Instead of just reporting MIB working modes, it reports modes based on working mode and battery status. Supported modes are:
Online: Power supply present on UPS input, load is battery protected. Bypass: Power supply present on UPS input, but load is NOT battery protected. Offline: Power supply is NOT present on UPS input, load is battery protected, battery charge is not low. Offline battery low: Same as previous but battery is low. Offline battery depleted: Power supply is NOT present on UPS i nput, battery is depleted so load is NOT protected.
Instead of using factory set battery low level threshold, user can select it using argument -l. Plugin return value is set comparing the current working mode with a comma separated working mode list set for triggering warning and critical states.
Plugin returns battery load percent and battery backup time (in minutes) as performance data.