Build precise queries to find exactly what you need
Press ESC to close
Your review has been submitted and is pending approval.
This 2 plugins for completly check PowerwWare UPS. check_xups_alarm: This plugin checks the active UPS alarms comparing them with both warning and critical alarm lists. It`s plugin rewrited and for PowerWare UPS (XUPS-MIB) from this http://exchange.nagios.org/directory/Plugins/Hardware/UPS/check_ups_alarms/details check_ups_pw.sh: Parser for check_snmp plugin (need XUPS-MIB) Recent change: check_ups_pw.sh (0.51): Add 255C bug catcher for xupsEnvAmbientTemp.0
Current Version
0.51
Last Release Date
2011-09-25
Owner
Artyom
Website
http://westcall.spb.ru
License
GPL
Compatible With
define command{ command_name ups_bat_cap command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatCapacity.0 -l 'Battery capacity' -w 90 -c 20 }
define command{ command_name ups_bat_sec command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o mib-2.33.1.2.2.0 -l 'Battery Runtime' -u 'sec' }
define command{ command_name ups_bat_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatVoltage.0 -l 'Battery Voltage' -u 'Volts' }
define command{ command_name ups_model command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsIdentModel.0 }
define command{ command_name ups_in_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsInputVoltage.1 -l 'Input Voltage' -u 'Volts' }
define command{ command_name ups_out_load command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputLoad.0 -l 'The UPS output load in percent of rated capacity' -u '%' }
define command{ command_name ups_out_walts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputWatts.1 -l 'The measured real output power' -u 'Watts' }
define command{ command_name ups_tem_input command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvAmbientTemp.0 -l 'Input temp' -u 'C' -w 38 -c 40 }
define command{ command_name ups_tem_remote command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteTemp.0 -l 'Output temp' -u 'C' -w 28 -c 30 }
define command{ command_name ups_bat_test command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsTestBatteryStatus.0 -l 'Battery test' -w 2 -c 2 }
define command{ command_name ups_humidity command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteHumidity.0 -l 'Humidity' -u '%' -w 80 -c 90 }
define command{ command_name ups_alarm command_line $USER1$/check_xups_alarms.pl -H $HOSTADDRESS$ -E1 -w 1..41 -c 3,4,7..16,23,26,27,29,31..36,39 }
You must be logged in to submit a review.
To:
From: